NH₃ vs CO₂ in industrial refrigeration

Angle noire

Understand, compare, choose

Faced with growing demands for performance, regulatory compliance, and environmental responsibility, industrial facility managers today must understand the technical and economic challenges of refrigeration systems.

This decision, far from being purely technical, directly affects the company’s operational profitability, facility safety, and carbon footprint.

NH₃ or CO₂? Key Factors for Choosing Your Natural Refrigerant

The choice of refrigerant is a strategic decision for any industrial refrigeration system. Two solutions are currently predominant in the industry: ammonia (NH₃) and carbon dioxide (CO₂). These are two “natural” refrigerants, found in nature and with a low environmental impact. However, their technical, economic, and regulatory characteristics differ.

In Quebec and Canada, the industry must balance energy efficiency, safety, compliance, and sustainability. This page outlines three steps: understanding each refrigerant, comparing them, and then choosing the right one for your facility. Neither option is the clear winner in every situation: your site decides.

What's in this guide

Physico-chemical properties

Ammonia (NH₃)
  • Chemical formula: NH₃
  • Boiling point: −28 °F (−33.3 °C) at atmospheric pressure
  • High cooling capacity by mass (high cooling capacity)
  • Non-miscible with oil, requires specific oil return management
  • Colourless, characteristic pungent odour: detectable at very low concentrations
Carbon dioxide (CO₂, R744)
  • Chemical formula: CO₂
  • Boiling point: -109.3°F (−78.5 °C) (sublimation), but used in liquid/gas form under controlled conditions (transcritical or subcritical cycle)
  • High density: enablescompact installations
  • Miscible with suitable oil
  • Odourless, colourless: detection using concentration sensors

Safety and risk management

NH₃: Effective, but with toxicological risks
  • Toxicity: Ammonia is toxic to humans even at low concentrations (Quebec TWA: 25 ppm, STEL: 35 ppm)
  • Flammability: slightly flammable at concentrations of 15 to 28% in air (Class B2L)
  • Easy to detect: very strong odour, leak can be detected quickly
  • Regulated management: strict standards for protection, ventilation, training, and emergency plans
CO₂: Increased Safety, but Beware of Asphyxiation
  • Non-toxic at usual concentrations, but risk of asphyxiation at high concentrations (gas heavier than air).
  • Non-flammable (Class A1)
  • Sensor-only detection
  • Very high operating pressures: requirements for equipment robustness and certification (up to 120 bar, or approximately 1,740 psi, in the transcritical range)

Energy performance

NH₃: Excellence in Efficiency and Extreme Cold Conditions
  • High coefficient of performance (COP), especially at low temperatures
  • Excellent efficiency for high-capacity installations (cold stores, agri-food industries, processing)
  • Suitable for prolonged operation and load variation
CO₂: Flexibility and Performance, Even in Cold Weather
  • Highly efficient for medium-temperature applications (commercial refrigeration, supermarkets, logistics warehouses)
  • In transcritical mode, the COP can be lower than NH₃ in hot weather, but in Quebec’s climate, performance is very competitive.
  • Compact systems: easily adaptable to urban areas or confined spaces

Environmental issues

NH₃ and CO₂: Responsible Choices
  • Global Warming Potential (GWP):
    NH₃ = 0.
    CO₂ = 1 (reference)
  • Non-destructive of the ozone layer
  • Both are favored by regulations (the Montreal Protocol, F-Gas), unlike HFCs with high global warming potential
Specific Regulatory Requirements
  • NH₃: Strict requirements regarding storage, ventilation, operator training, and emergency plans (CNESST, CSA B52). Certification of high-pressure equipment is required depending on the sector.
  • CO₂: The Need for Certification of High-Pressure Equipment, Appropriate Detection Protocols, and Ventilation Systems

Regulations Specific to Quebec: Requirements, Obligations, and Differences Based on the Fluid

In Quebec, regulatory oversight of refrigeration systems is particularly rigorous, for both ammonia (NH₃) and carbon dioxide (CO₂). Companies must comply with a patchwork of laws, regulations and technical standards designed to protect the health and safety of the public, workers and the environment.

NH₃ (Ammonia) regulations in Quebec

  • Act respecting occupational health and safety (AOHS) and Regulation respecting occupational health and safety (RROHS): As ammonia is classified as a hazardous substance (toxicity, flammability), all installations must be subject to a risk analysis, an emergency measures plan, and specific signage.
  • CSA Code B52 (Mechanical Refrigeration Code), which applies in the province, imposes stricter requirements on:
    • Design and installation (distance from populated areas, ventilation requirements, materials)
    • Ammonia leak detection (automatic systems, alarms, periodic maintenance)
    • Containment and consequence limitation protocols in the event of a leak
  • CNESST (Commission des normes, de l’équité, de la santé et de la sécurité du travail): Mandatory inspection of pressure installations, operator training, incident reporting.
  • Emergency Plan: Facilities of a certain size must file an emergency response plan with local authorities (municipality, fire department). This applies in particular to municipal arenas that use ammonia.

CO₂ (Carbon Dioxide) regulations in Quebec

  • CSA Code B52 also applies to CO₂, with specific requirements on equipment robustness (certified high-pressure equipment), ventilation of technical rooms, and drain management.
  • Asphyxiation risks: As CO₂ is heavier than air, concentration detectors and suitable ventilation systems are required in enclosed premises.
  • Inspection of pressure equipment: even though CO₂ is non-toxic and non-flammable, installations operating at high pressure must be declared to the RBQ (Régie du bâtiment du Québec) and inspected periodically.
Document management and traceability
  • For both fluids, the following must be kept up to date: inspection and maintenance logs, leak and repair reports, operator training records, and equipment compliance and certification records
Soteck Clauger tip:
  • Using a digital portal such as MyPortal3E greatly simplifies document management, preparation for CNESST/RBQ inspections, and responsiveness in the event of an audit or incident report.
Summary of Regulations
  • NH₃: Much stricter and more restrictive regulations (due to its toxicity), as well as increased requirements for training, emergency planning, and risk management.
  • CO₂: Regulations focused on pressure equipment and asphyxiation prevention, similar documentation requirements but working environments perceived as less risky.

Summary table

CRITERIA NH₃ (Ammonia) CO₂ (Carbon dioxide)
Security
Toxicity, emergency plans, mandatory training, detection, evacuation plans
Risk of asphyxiation, CO₂ detection, ventilation mandatory
Quebec regulations
Very strict: CNESST, CSA B52, emergency plan, incident reporting, RBQ
CSA B52, RBQ, pressure equipment control, ventilation management
Document management
Mandatory, leak register, inspections, training
Mandatory, inspection and maintenance log
Other bonds
Submission of municipal response plan, risk analysis, containment measures
Declaration of pressure equipment, periodic inspection

Investment and operating costs

NH₃: Initial investment, but a quick return on investment
  • Higher installation costs (safety features, training, advanced automation)
  • Specific maintenance (oil management, seal monitoring)
  • Long plant life and low fluid costs
  • Attractive ROI on high-load refrigeration systems (sometimes <3 years)

CO₂: Competitive and Scalable
  • Compact systems, fast installation, competitive costs for medium to large installations
  • Maintenance without toxic hazards; more thorough leak detection due to high pressure
  • Low fluid costs, but more expensive pressurized equipment
  • Ideal for extending or modernizing existing sites

Innovation, Oversight, and Digitization

The digitization of facilities (monitoring, predictive maintenance, document management) is now a key differentiator.

Integrating tools such as MyPortal3E provides the same added value for monitoring, optimization, and compliance, whether you choose NH₃ or CO₂.

  • For NH₃: enhanced incident monitoring, emergency plan management, and traceability of critical maintenance tasks
  • For CO₂: precise monitoring of transcritical cycles, consumption optimization, and streamlined document management

In summary: Choose based on your specific needs andconstraints

CRITERIA NH₃ (Ammonia) CO₂ (Carbon dioxide)
Security
Highly regulated, toxic
Secure, but beware of asphyxiation
Energy efficiency
Excellent, especially in very cold weather
Very good, flexible, efficient in Quebec
Installation cost
Higher, faster ROI
Moderate to high flexibility
Maintenance
Specific, training required
Standardized, more thorough leak detection (high pressure)
Environment
GWP = 0
GWP = 1, no impact Ozone
Regulations
Very strict (emergency plans, etc.)
Specific (pressure, detection)
Adaptability
Large installations
Small/medium/large, urban
Digitization (MyPortal3E)
Optimizing safety and compliance
Performance and compliance monitoring

FAQ:Frequently Asked Questions About Choosing Between Ammonia and CO₂

Plant managers and process engineers often ask us these eight questions. They come up most frequently when deciding between ammonia and transcritical CO₂. Each answer is based on a standard, a threshold, or a study cited as a source.

These answers provide general guidelines, not absolute truths. Your process, production volumes, and heat requirements may affect the conclusion. Before making any decisions, we consider each answer in the context of your facility.

4.50 tonnes or more of anhydrous ammonia, according to federal regulations. For an ammonia solution of 20% or more, the threshold increases to 9.10 tonnes. The Environmental Emergency Regulations, 2019 set these values in Schedule 1 (1).

There are two triggers, and only one is needed. The first is the actual quantity on hand. The second is the maximum capacity of the container system, even when it is not full.

Once the threshold is reached, the notice to the minister is sent within 90 days. The emergency plan is developed within 6 months and implemented within 12 months. This is followed by an annual simulation exercise and a full-scale drill every 5 years. The plan is also reviewed annually.

A plant designed below this threshold avoids this entire cycle. When the process allows, a secondary CO₂ loop helps achieve this. The ammonia load then remains confined to the machine room. The exact calculation is done site by site, container by container.

Not necessarily: in the only known Canadian study with specific figures, it consumes less. CanmetENERGY Varennes modelled twelve systems at a reference arena in Montreal (12). Taking both cooling and heating into account, the best CO₂ system consumes 381,600 kWh per year. The reference ammonia system consumes 542,400 kWh, and the older R-22 system consumes 1,019,500 kWh.

The difference between CO₂ and ammonia is 25 to 30%. Most of the savings come from heat recovery. Heat recovery alone reduces consumption by more than 40%.

These results cannot be directly applied to a factory. The study focuses on arenas, and the load profiles of a food processing plant are different. The actual benefit depends largely on what the plant does with the waste heat. If there is no on-site need for heat, the advantage of CO₂ may diminish.

Transcritical CO₂ often offers advantages in three situations. First, a plant that wants to remain below the regulatory threshold for ammonia. Second, a need for hot water at temperatures above 70 °C, for pasteurization or cleaning-in-place. Finally, a cramped machine room, where managing the risk of inhalation is costly.

Quebec’s climate also works in CO₂’s favour. Its critical point is 31.03 °C and 73.80 bar (7). The colder the climate, the longer the system remains in the subcritical operating range. This results in better annual efficiency.

The technical literature places the “CO₂ equator” between 14.1 and 18.9 °C as an annual average (9). Quebec lies well north of this range.

Ammonia often has the edge when it comes to very high cooling capacities at stable sub-zero temperatures. For the storage of apples, which release CO₂, ammonia is generally the preferred choice. In any case, these trends are confirmed by a site survey.

Both refrigerants are covered by the same code: the CSA B52 Mechanical Refrigeration Code. The Pressure Equipment Regulations refer to this code for both manufacturing and installation. They refer to the most recent published edition, without specifying its title (2). The work requires an RBQ licence, subclass 15.10, refrigeration contractor.

The difference lies in the security classification (6). Ammonia is classified as B2L: higher toxicity, low flammability. CO₂ is classified as A1: low toxicity, no flame propagation. The time-weighted average exposure limit ranges from 25 ppm for ammonia to 5,000 ppm for CO₂ (3).

This ranking doesn’t tell the whole story. Ammonia has a pungent odour that can be detected even at very low concentrations: a leak is quickly noticed. CO₂, on the other hand, is odourless and colourless. Without a sensor, a leak goes unnoticed, and the gas accumulates in low-lying areas (14).

In apple storage, for example, the fruit itself emits CO₂. The storage room is already equipped with a CO₂ detection system. Using CO₂ as a refrigerant would interfere with this monitoring. Instead, the preference is for ammonia, even though its heat recovery is sometimes less efficient.

As for halocarbons, a Quebec ban has been in effect since January 1, 2021. It applies to food storage appliances rated at 50 kW or more. The global warming potential of their refrigerant must not exceed 150. Processing operations are exempt (4).

In reality, the remaining substances are ammonia, CO₂, hydrocarbons, and certain HFOs.

It all depends on the operating mode and the site’s heat demand. At some facilities, it’s more efficient to run the compressors for longer periods. This allows their heat to be recovered instead of starting up an electric boiler. The optimal balance is determined based on the volumes and needs of each site.

The following figures are taken from the literature and serve as reference points. In transcritical CO₂, the compressor discharge temperature ranges from 80 to 120 °C (8). Approximately 80% of the available heat between 100 and 25 °C is recovered. The additional compression work remains limited.

Bypassing the gas cooler recovers all the heat, but lowers the coefficient of performance (COP). Standard settings heat domestic hot water to 55 °C and heating water to 40 °C.

As for ammonia, industrial heat pumps reach approximately 90 °C at the heat sink (11). Compressors with cast-steel housings can withstand pressures up to 76 bar and temperatures up to 110 °C.

A 2025 study on dairy processing targets 72 °C and 50 kW for pasteurization (10). The excess heat is used for cleaning-in-place. In this study, parallel compression improves the COP by 19.1%, and the ejector by 32.4%. Combined, the two achieve a 62.3% improvement.

They remain legal, but the new-construction market is largely off-limits to them. Since January 1, 2020, the federal global warming potential limit has been 2,200. It applies to the importation and manufacture of centralized systems and condensing units. For chillers, the limit will drop to 750 on January 1, 2025 (5).

R-404A has a value of 3,922 according to Canadian regulatory standards, while R-134a has a value of 1,430. CO₂ is at 1 and ammonia at 0. The Canadian cap on HFC consumption continues to decline. It will drop to 30% of the baseline in 2029, 20% in 2034, and 15% as early as 2036 (5).

Top-up refrigerant may therefore become scarcer and more expensive. Switching from R-404A to another HFC with high global warming potential does not eliminate this risk. The right time to convert depends on the condition of the unit and your plans. A reliable, leak-free unit can sometimes wait until the next major overhaul.

For leak detection, yes. The pressure range is the main difference between the two refrigerants. A CO₂ system typically operates between 35 and 100 bar, up to 120 bar in transcritical mode. Ammonia operates at much lower pressures.

1Our teams therefore apply a more rigorous leak detection procedure for CO₂. Extended shutdowns also require a pressure-maintenance unit. Safety equipment remains mandatory in both cases. This includes detection, ventilation, and fire resistance in the engine room.

Ammonia, on the other hand, poses a greater risk in terms of emergency procedures. Its engine room requires an emergency response plan and a dedicated mechanical ventilation system. Detection there occurs at two levels. At concentrations above 300 ppm, self-contained breathing apparatus becomes mandatory.

The CNESST guide recommends exercises with breathing apparatus every three months (13). The response team trains every six months. In both cases, the work is performed by a contractor holding an RBQ 15.10 licence (2). The plant team receives training on its specific system, not on the refrigerant in general.

The actual maintenance requirements always depend on the size and design of the system. Our technicians will be on site within four hours, 24 hours a day.

1Through a site-specific analysis based on your specific challenges. No spreadsheet can replace an understanding of your volumes, projects, and constraints. However, four key pieces of information guide the initial discussion.

First, cooling capacity and temperature range. At temperatures below −40 °C and for capacities exceeding a few megawatts, ammonia is often hard to beat. Next, heat demand. A plant that pasteurizes or washes with hot water would benefit from exploring transcritical CO₂.

A high-temperature heat pump is another option to consider. Third factor: the target ammonia charge, relative to the 4.50-metric-ton threshold. Finally, the space required in the machine room, which affects the cost of compliance.

Our Flash Audit provides this initial assessment in just one day, with no obligation. It also identifies available grants. The subsequent study refines the recommendations based on your operational challenges.

Content approved by:

Picture of jonathan desmars

Jonathan Desmars

Sales and Development Manager
, Industrial Refrigeration & HVAC

View his full profile

Nearly 20 years in the refrigeration industry. His career has spanned from electromechanical refrigeration to marine refrigeration, and then to industrial agri-food refrigeration. He oversaw the first scheduled shutdown of an ammonia condenser carried out by Soteck Clauger. He also led the first complete mechanical overhaul in the workshop.

This page was written on November 8, 2026, using sources consulted in October and November 2026.

To contact Jonathan

Conclusion and Sources

1Industrial refrigeration using ammonia or transcritical CO₂: equipment costs alone are not enough to make a decision. This is true for food processing plants, cheese factories, slaughterhouses, and cold storage facilities alike. Capacity, hot water requirements, ammonia charge, and machine room layout are key considerations. However, these criteria do not replace a thorough site assessment and analysis of its operational constraints.

Each natural refrigerant has its own requirements for pressure, detection, and maintenance. CO₂, which is odourless, is monitored by sensors; ammonia is detected by its odour. Two regulations come into play from the design phase onward: environmental emergencies and halocarbons. CSA Code B52 governs manufacturing and installation, regardless of the technology chosen.

The right decision is made before the plans are drawn up, based on measurements taken on site. A heat recovery calculation for the refrigeration unit rounds out the process. Our Flash Audit provides an initial assessment in just one day, including available grants. Once in service, MyPortal3E ensures the traceability of inspections and leak detection efforts.

Sources 01 through 13 were consulted on October 8, 2026; source 14 was consulted on November 8, 2026. No specific edition of CSA B52 is mentioned in the text: the Pressure Vessel Regulations refer to “the most recent published edition” without identifying it, and the current edition remains to be confirmed with the Régie du bâtiment du Québec. The GWP values cited are those adopted by Canadian regulations, not those from the latest IPCC report, so that the figures align with the thresholds cited.

  1. Government of Canada, Environmental Emergencies Regulations (2019), SOR/2019-51, Schedule 1 and sections 3 through 14. View the regulations
  2. Government of Quebec, Regulation respecting pressure vessels, RLRQ Chapter B-1.1, R. 6.1, Sections 3, 6, 7, 10, and 62. View the rules
  3. Government of Quebec, Occupational Health and Safety Regulation, RLRQ Chapter S-2.1, Rule 13, Appendix I, Permissible Exposure Limits. View the rules
  4. Government of Quebec, Halocarbons Regulation, RLRQ Chapter Q-2, Reg. 29, Sections 21.1 and 21.2. View the rules
  5. Government of Canada, Ozone-Depleting Substances and Alternative Halocarbons Regulations, SOR/2016-137, Schedule 1.1 and HFC Phase-Down Schedule. View the regulations
  6. ASHRAE, ANSI/ASHRAE Standard 34, Designation and Safety Classification of Refrigerants, Public Addendum, 2022. View the standard
  7. National Institute of Standards and Technology, NIST Chemistry WebBook, carbon dioxide data sheet, phase transition data. View the entry
  8. Danfoss, Heat Recovery in Transcritical CO2 Systems, Application Guide DKRCE.PA.R1.F1.22, 2015. View the guide
  9. Paride Gullo, Armin Hafner, Krzysztof Banasiak, Silvia Minetto, and Ekaterini E. Kriezi, “Multi-Ejector Concept: A Comprehensive Review of Its Latest Technological Developments,” *Energies*, vol. 12, no. 3, article 406, 2019. Read the article
  10. Pramod Singha, Chandan Das, Mani Sankar Dasgupta, Souvik Bhattacharyya, and Armin Hafner, “A New Approach to Improve COP and Heat Recovery in a Transcritical CO₂ Refrigeration System for Milk Processing Applications,” Scientific Reports, Volume 15, Article 5502, 2025. Read the article
  11. Benjamin Zühlsdorf et al., High-Temperature Heat Pumps, Task 1, Technologies, International Energy Agency, HPT TCP Annex 58 programme, Report HPT-AN58-2, 2023. View the report
  12. Natural Resources Canada, CanmetENERGY Varennes, Comparative Study of Refrigeration Systems for Ice Rinks, 2013. View the study
  13. CNESST, Ammonia-Based Refrigeration Systems, Preventive Measures. The guide also refers to CSA B52-05; the detection thresholds must be re-validated against the current edition. 1View the guide
  14. Canadian Centre for Occupational Health and Safety (CCOHS), Carbon Dioxide, OHS Answers, Chemical Profile, updated January 16, 2024. View the fact sheet